Q&A: The man who helped raise server operating temperatures
It's been a year since an engineering body said it was safe to raise the operating temperatures of servers and storage systems.
Computerworld - Next month is the one year anniversary of a guideline by the American Society of Heating Refrigerating and Air-Conditioning Engineers (ASHRAE) that recommend increasing (PDF document) the temperature of air entering servers and other data center equipment. This increase of 77 degrees Fahrenheit to 80.6 degrees may not seem like a big deal, but it took a year-and-half of work to arrive at this recommendation and agreement by most of the major equipment vendors. The person who led the society's IT team on Technical Committee 9.9 was Roger Schmidt, an IBM fellow and its chief engineer for data center energy efficiency.
It's unknown how many data centers have adopted the recommendation, or even have enough control over their environments to safely regulate air flows. Ken Brill, executive director of the Uptime Institute in Santa Fe, New Mexico, said he sees more understanding that the data center temperatures can go up and says there has been a "very significant attitudinal change in a year," he said, but adds, that "many still don't know."
In an interview, Schmidt looked at the new temperature parameters, as well as some other issues involved in cooling data centers and reducing power usage.
How much heat can servers handle before they run into trouble? The previous guidelines for inlet conditions into server and storage racks was recommended at 68 degrees Fahrenheit to 77 Fahrenheit. This is where the IT industry feels that if you run at those conditions you will have reliable equipment for long periods of time. There is an allowable limit that is much bigger, from 59 degrees Fahrenheit to 89 degrees. That means that IT equipment will operate in that range, but if you run at the extremes of that range for long periods of time you may have some fails. We changed the recommended level -- the allowable levels remained the same -- to 64F to 81F. That means at the inlet of your server rack you can go to 81 degrees -- that's pretty warm. [The standard also sets recommendation on humidity levels as well.]
What made it possible to change the recommendation? It took a year-and-half of all the IT manufacturers talking through this and making sure we had what we felt was some hard data behind this that would meet the new requirements.
Since this standard went out one year ago, what's been the adoption of it? Some are starting to use it. We [IBM] are starting to internally use it. It's something that's not going to happen overnight. They [data center managers] will probably step it up two degrees at a time. The benefit will be contingent on an analysis for that data center on what happens if you raise the air temperature and thereby raise the chilled water temperature by "x" amount. Raising the temperature allows you to possibly to turn off the chiller for a longer period time and use outside ambient air to cool your data center. In general, it's like raising the thermostat in your house.



- Excel 2010 Cheat Sheet
- Register for this Computerworld Insider Cheat Sheet and gain access to hundreds of premium content articles, guides, product reviews and more.
- Optimize Data Backup to Ensure Data Protection
- Protecting data, a top IT priority, is made even more difficult as rapid data growth pushes traditional backup processes beyond their capabilities. Integrating...
- Enabling Storage Flexibility to Better Manage Data Growth
- Virtualizing file storage gives organizations the flexibility and data mobility required to reduce backup windows and costs, improve storage efficiency, and seamlessly integrate...
- Case Study: Publisher Cuts Backup Times by 98 Percent
- Learn how John Wiley & Sons, Inc., a leading publisher for scientific, technical, and medical communities, successfully reduced backup times from 36 hours...
- Case Study: Firm Optimizes Storage, Shrinks Backup Window
- By optimizing its existing storage environment, multi-skilled architectural firm RHWL reduced backup times from 14 hours to 1.5 hours, slashed tape and offsite...
- Indiana University Virtualizes Mission-Critical Oracle Databases
- The Kelley School of Business at Indiana University deployed VMware Infrastructure which decreases costs, streamlines server deployment, and reduces energy consumption. All Data Center White Papers
- Live Webcast
North Pole to South Seas: Overcoming the Pitfalls of remote Performance - In today's always-on world, connectivity is a business requirement. You need the tools that allow you to operate as if you were on...
- Live Webcast
Playing Defense: Staying on Top of Your Disaster Recovery Game - When it comes to disaster recovery, rapidly growing data volumes, distributed computing models, and new technologies all combine to present an ever-changing playing...
- Customer Spotlight: How IPC The Hospitalist Company Implemented Oracle on VMware
- Have you been looking to hear about customer's experiences with the new VMware vCenter Site Recovery Manager product? View this webcast to learn...
- Introduction to VMware View 5
- VMware View™ 5 simplifies IT management while increasing end user freedom by delivering desktop services from your cloud. Building upon VMware's leadership in...
- Reliable Disaster Protection with VMware vCenter Site Recovery Manager
- A simple, cost-effective disaster-recovery solution for virtual environments is high on the agenda for IT organizations as they virtualize more business-critical applications with...
- Introduction to VMware vCenter Site Recovery Manager 5
- Traditional disaster recovery solutions are often too expensive, complex and unreliable to meet business requirements. As a result, IT departments are hesitant to...
- Introduction to Virtualization
- This video webcast is designed to help those with little to no virtualization experience understand why virtualization and VMware are so important to... All Data Center Webcasts